Specification

Output Specification
Output Capacity (KVA )
6 Kva
Output Capacity (KW )
6 KW
Output Power Factor
1 Power Factor
Output Phase
1 Phase
Output Voltage
230 Volt
Other Output Voltage
200 Or 240 Volt
Efficiency at Full Load
>90 %
Output Voltage Distortion
<3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor
3:1
Output Voltage THD
<3 %
Output Waveform type
Sine Wave
UPS Parallel Upto
4 Nos.
Input Specification
Input Voltage
230 Volt
Other Input Voltage
200 Or 264 Volt
Input Phase
1 Phase
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
100 - 285 Volt
Input voltage range for main operations
140 - 280 Volt
Input frequency Range
40 - 70 Hz
Input Power Factor
>0.99 None
Batteries & Runtime
Battery DC Bus
192 - 240 VDC
Maximum Charger Capacity
8 Amp.
Battery Position Option
External
Battery Type Compatibility
SMF Battery
Approved Battery Capacity (AH)
7 - 200 Amp.
Communication & Management
Control panel
LCD Display
SNMP Management
Optional
Power Management Software
In-Built
Interface Port(s)
RS-232, USB
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
<50 Decibal
Physical
Maximum Height
325 Mm
Maximum Width
190 Mm
Maximum Depth
390 Mm
Net Weight
10.1 Kg
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
5 - 95 % Rh
Other Specifications
Technology
Double Conversion Online

Features

Amplon New N Series 6-10 KVA Features
The Most Compact Design and Best TCO
The smallest dimensions in its class saves significant space for more critical equipment.
A pioneer in unity power factor (kVA=kW) to maximize power availability.
The highest AC-AC efficiency up to 95% and efficiency of 98% in ECO mode for exceptional energy cost savings
Automatic speed regulation function with multi-stage fan speed control maximizes system efficiency, significantly reduces audible noise, and prolongs the service life of the fans
Availabilty
True online double-conversion topology and zero transfer time to battery ensure high reliability
Parallel configuration for expansion and N+X redundancy up to 4 units.
Advanced DSP (Digital Signal Processor) controller for fast computation capabilities and a simplified control circuit for enhanced stability.
Generator compatibility ensures continuous and reliable power
Intelligent Management
Excellent local communications through user friendly LCD display
Intelligent battery management sustaining battery life and performance
Various types of communication interfaces enhance monitoring and manageability.