Contact Us

Brand DELTA UPS System Industrial UPS Delta Make 30 KVA 3:3 Phase Industrial On-Line UPS With Isolation Transformer ( HPH Series )

Delta Make 30 KVA 3:3 Phase Industrial On-Line UPS With Isolation Transformer ( HPH Series )

UPS System Industrial UPS

Price: 460200

You save 712366

Model Ultron HPH-30kVA Iso-Tx

Reset default

Specification

Output Specification
Output Capacity (KVA )
30 KVA
Output Capacity (KW )
30 KW
Output Power Factor
1 Power Factor
Output Phase
3 Phase
Output Voltage
400 Volt
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 95 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Load Crest Factor
3:1
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Maintenance Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
UPS Parallel Upto
4 Nos.
Input Specification
Input Voltage
400 Volt
Other Input Voltage
380 Or 415 Volt
Input Phase
3 Phase
Input frequency
50 Or 60 Hz
Input frequency Range
45 - 65 Hz
Input Voltage Range (Output Derated)
277 - 485 Volt
Input voltage range for main operations
304 - 477 Volt
Input Power Factor
0.99
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Voltage THD
< 3 %
Batteries & Runtime
Battery DC Bus
384 - 600 VDC
Battery Type Compatibility
SMF / Flooded Batteries
Battery Position Option
External
Approved Battery Capacity (AH)
26 - 200 Amp.
Battery Circuit Breaker
Optional
Communication & Management
SNMP Management
Optional
Power Management Software
Optional
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
< 60 Decibal
Physical
Maximum Height
800 Mm
Maximum Width
380 Mm
Maximum Depth
800 Mm
Net Weight
86.06 Kg
Environmental
Operating Relative Humidity
0 - 95 %
Protection Class
IP20
Operating Temperature
0 - 40 °C
Other Specifications
Technology
Double Conversion Online

Features

Ultron HPH Series Features
Efficiency & Reliability
Fully rated power (kVA=kW) for maximum power availability
Leading AC-AC efficiency up to 96% saves energy costs
Low harmonic pollution (iTHD<3%) & high input power factor (>0.99) reduce upstream investment costs
Assured Reliability
Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life
DSP based technology enables reduction in the number of electronic components to lower failure rate
Redundant auxiliary power and fan design* enhance system reliability ( * Applied for models HPH-60/80/100/120K )
Watch-dog design of the DSP (Digital Signal Processor) increases reliability
Built-in manual bypass ensures continuous power to the load even if the UPS is under maintenance
Flexibility
A wide input voltage range of up to 305~477V to reduce battery discharge probability and prolong battery life.
Adjustable charging current and battery voltage meet different battery configuration requirements
Flexible battery configuration optimizes battery investment
Manageability
Swappable interior architecture and front access servicing enables quick and easy maintenance* ( * Applied for models HPH-60/80/100/120K )
Multi-connectivity interface supports remote UPS monitoring and management

Documentation

Item Catalogue
Leaflet-UPS-HPH-20-120kW-en-us
pdf
Item Manuals and Warranties
HPH Series 20-40 kW User Manual
pdf

Options